ITEM |
Standard test Method |
ASTM Spec |
Conductive Tile |
|
ELECTRICAL / ELECTROSTATIC PROPERTIES
|
Electrical Resistance
-Surface to Surface
-Surface to Ground |
ESD
S 7.1 (100V / 10V)
ASTM F-150 (100V / 10V)
NFPA 99 (500V)
DIN 51953 (500V) |
>2.5 X 104~<106Ω
|
2.5 X 104~106
|
|
>2.5 X 104
|
>2.5 X 104 ~ <8.3
X 105Ω
|
Electrostatic Propensity
(=Static Generation) |
AATCC 134
With heel grounders
|
-
|
<25 volts
|
|
Static Decay |
Federal Test
Method 101B Method 4046 at 15% Relative Humidity |
< 0.5 sec
|
<0.01 sec
|
|
OTHER
PROPERTIES |
| CEN
Classification |
DIN EN 685 |
|
Class 34 + 43
|
|
Composition of Material |
ASTM F 1700
Certificate of Compliance |
|
Homogeneous
|
|
Thickness |
ASTM F 386, DIN
EN 428 |
as specified ±0.005 in.
(.125)
|
.125
|
|
Nominal Sizes |
ASTM F 536, DIN
EN 427 |
±0.016 in./lin. Ft
(0.4mm/304.8 mm)
|
12" x 12" standard
24" x 24" optional
|
|
Squareness |
ASTM F 540 |
maximum 0.010 in. (0.25 mm)
|
<0.010"
|
|
Residual Indentation |
ASTM F1914
DIN EN 433 |
average less than 8%,
max. single reading 10%
|
< 7%
|
| Flexibility |
ASTM F 137 |
no crack or break
|
No crack or break
|
|
Dimensional Stability |
ASTM Fed. Std.
No. 501a
Method 6211, DIN EN 434 |
<0.020"/ft (0.51 mm/304.8 mm)
|
<0.015"/ft
|
|
Resistance to Chemicals |
ASTM F 925
DIN EN 423 |
No more than a slight change
in surface dulling, surface attack or
staining
|
no more than a slight change
in surface dulling, surface attack, or
staining
|
|
Resistance to Heat |
ASTM F 1514 |
∆<8 ave., max
|
<∆E=2.0
|
|
Resistance to Light |
ASTM F 1515 |
∆E<8 ave., max
|
<∆E=6.0
|
|
Static Load Limit |
Modified ASTM F
970-00 |
-
|
>2,500 psi
|
|
Smoke Density |
ASTM E 662 |
<450
|
<450
|
|
Flame Spread |
ASTM E 84, NFPA
225 |
<75
|
<75
|
| Fire
Resistance |
DIN 4102 |
|
B1
|
|
Critical Radiant Flux |
ASTM E 648, NFPA
253 |
|
>1.08 W/cm2(class
I Interior Floor Finish, NFPA Life Safety
code 101)
|
|
Abrasion Resistance |
ASTM D 1044,
CS-10-F Wheel,
500Gm Weight |
|
|
Cycle
10,000
|
% Gauge Loss
1.60
|
|
|
Resistance to Wear |
DIN EN 660-1 |
|
M
|
|
Effect of Castor Chair |
DIN En 425 |
|
No Damage
|
|
Color Fastness |
ISO 105 B02 |
|
At least 6
|
|
Standard for Health Care Faculties |
NFPA 99 |
|
Confirms to the requirements
of NFPA 99 in effect at the time of
installation
|
|
Fulfils product requirements |
DIN EN 649 |
|
yes
|
|
Underwriters Laboratories |
UL 779 |
|
Meets UL Standard
|
|
WARRANTY
|
| Free
from defects in Workmanship and materials* |
|
|
Lifetime
|
|
Conductivity* |
|
|
Lifetime
|