ITEM |
Standard test Method |
ASTM Spec |
Conductive Tile |
|
ELECTRICAL / ELECTROSTATIC PROPERTIES
|
Electrical Resistance
-Surface to Surface
-Surface to Ground |
ESD
S 7.1 (100V / 10V)
ASTM F-150 (100V / 10V)
NFPA 99 (500V)
DIN 51953 (500V) |
>2.5 X 104~<106Ω
|
2.5 X 104~106
|
|
>2.5 X 104
|
>2.5 X 104 ~ <8.3
X 105Ω
|
Electrostatic Propensity
(=Static Generation) |
AATCC 134
With heel grounders
|
-
|
<20 volts
|
|
Static Decay |
Federal Test
Method 101B Method 4046 at 15% Relative Humidity |
< 0.5 sec
|
<0.01 sec
|
|
OTHER
PROPERTIES |
|
CEN
Classification |
DIN EN 685 |
|
Class 34 + 43
|
|
Composition of Material |
ASTM F 1700
Certificate of Compliance |
|
Homogeneous
|
|
Thickness |
ASTM F 386, DIN
EN 428 |
as specified ±0.005 in.
(.125)
|
.125
|
|
Nominal Sizes |
ASTM F 536, DIN
EN 427 |
±0.016 in./lin. Ft
(0.4mm/304.8 mm)
|
12" x 12", 24" x 24"
|
|
Square Tolerance |
ASTM F 540 |
maximum 0.010 in. (0.25 mm)
|
<0.010"
|
|
Residual Indentation |
ASTM F1914
DIN EN 433 |
average less than 8%,
max. single reading 10%
|
< 7%
|
|
Flexibility |
ASTM F 137 |
no crack or break
|
No crack or break
|
|
Dimensional Stability |
ASTM Fed. Std.
No. 501a
Method 6211, DIN EN 434 |
<0.020"/ft (0.51 mm/304.8 mm)
|
<0.015"/ft
|
|
Resistance to Chemicals |
ASTM F 925
DIN EN 423 |
No more than a slight change
in surface dulling, surface attack or
staining
|
no more than a slight change
in surface dulling, surface attack, or
staining
|
|
Resistance to Heat |
ASTM F 1514 |
∆<8 ave., max
|
<∆E=2.0
|
|
Resistance to Light |
ASTM F 1515 |
∆E<8 ave., max
|
<∆E=6.0
|
|
Static Load Limit |
Modified ASTM F
970-00 |
-
|
>2,500 psi
|
|
Smoke Density |
ASTM E 662 |
<450
|
<450
|
|
Flame Spread |
ASTM E 84, NFPA
225 |
<75
|
<75
|
|
Fire
Resistance |
DIN 4102 |
|
B1
|
|
Critical Radiant Flux |
ASTM E 648, NFPA
253 |
|
>1.08 W/cm2(class
I Interior Floor Finish, NFPA Life Safety
code 101)
|
|
Abrasion Resistance |
ASTM D 1044,
CS-10-F Wheel,
500Gm Weight |
|
|
Cycle
10,000
|
% Gauge Loss
1.60
|
|
|
Resistance to Wear |
DIN EN 660-1 |
|
M
|
|
Effect of Castor Chair |
DIN En 425 |
|
No Damage
|
|
Color Fastness |
ISO 105 B02 |
|
At least 6
|
|
Standard for Health Care Faculties |
NFPA 99 |
|
Confirms to the requirements
of NFPA 99 in effect at the time of
installation
|
|
Fulfils product requirements |
DIN EN 649 |
|
yes
|
|
Underwriters Laboratories |
UL 779 |
|
Meets UL Standard
|
|
WARRANTY
|
|
Free
from defects in Workmanship and materials* |
|
|
Lifetime
|
|
Conductivity* |
|
|
Lifetime
|
CHEMICAL RESISTANCE EXPOSURE
TIME 1 HOUR ELECTRICAL RESISTANCE
Sulfuric Acid (Conc.) 95%
Sulfuric Acid (77%)
Sulfuric Acid (5%)
Nitric Acid (Conc.)
Nitric Acid (5%)
Hydrochloric Acid (Conc.)
Hydrochloric Acid (5%)
Acetic (Conc.)
Acetic (5%)
Sodium Hydroxide (50%)
Ammonium Hydroxide (28%)
Methyl Alcohol
Ethyl Alcohol
Butyl Alcohol
Phenol
Benzene
Xylene
Cresol
Gasoline, Mineral Oil
Chloroform
Carbon Tetrachloride
Trichlorethylene
Acetone
Methyl Ethyl Ketone
Amyl Acetate, Ethyl Acetate
Silver Nitrate (40%)
Ethyl Ether
Formaldehyde (40%)
Iodine |
Slight Surface attack
No effect
No effect
Very slight surface attack
No effect
No effect
Very slight dulling
No effect
No effect
No effect
Slight
Discoloration
No effect
No effect
No effect
Very slight surface attack
No effect
No effect
Very slight surface attack
No effect
No effect
No effect
No effect
No effect
Slight surface dulling
Slight surface
dulling
Slight brown stain
No effect
No effect
Yellow stain |
ElectraTile RTG Resistance Testing,
as
installed, facility 1

Click for installed
RTG, Testing by United
SERIES: Conductive
ELECTRICAL PROPERTIES:
ASTM 150/EOS/ESD S7.1
RTG: 2.4E04 to 8.3 E05 |
|
ElectraTile PTP Resistance Testing, as
installed, facility 2

Click for installed
Point to Point, Testing by United
SERIES: Conductive
ELECTRICAL PROPERTIES:
ASTM 150/EOS/ESD S7.1
PTP: 2.5E04 to 9.9E05 |
CONTACT
United STATIC CONTROL PRODUCTS!
United Static Control Products
P.O.B. 19252, 4878 Lake View Circle
Colorado City, CO 81019
United States of America
Phone: 719 676
3928 Fax: 719 676 3929
24/7
Tech Support (customers only)
719
676 3928 (option 8)
Major Credit Cards Accepted
© 1993-2010
All rights Reserved
ESD Flooring,
Mats, Chemicals,
ESD
Ionizers,
and
Expertise
United SCP Tames the Static Beast BEFORE it Takes Another Byte
This page last updated on
05/10/2010
|