ElectraTile Main Page

 

SELECT ESD flooring MATERIAL OPTIONS

 

 ElectraTile Conductive ESD Floor Tile
ISO CERTIFIED, S2020 Compliant, UL Listed

ITEM Standard test Method ASTM Spec Conductive Tile
ELECTRICAL / ELECTROSTATIC PROPERTIES
Electrical Resistance
-Surface to Surface

-Surface to Ground
ESD S 7.1 (100V / 10V)
ASTM F-150 (100V / 10V)
NFPA 99 (500V)
DIN 51953 (500V)
>2.5 X 104~<106Ω
 
2.5 X 104~106

 
>2.5 X 104
>2.5 X 104 ~ <8.3 X 105Ω
 Electrostatic Propensity
(=Static Generation)
AATCC 134
With heel grounders
-
<20 volts
 Static Decay Federal Test Method 101B Method 4046 at 15% Relative Humidity
 < 0.5 sec
 <0.01 sec
 OTHER PROPERTIES
CEN Classification DIN EN 685  
Class 34 + 43
Composition of Material ASTM F 1700
Certificate of Compliance
 
Homogeneous
Thickness ASTM F 386, DIN EN 428
as specified ±0.005 in. (.125)
.125
Nominal Sizes ASTM F 536, DIN EN 427
±0.016 in./lin. Ft (0.4mm/304.8 mm)
12" x 12", 24" x 24"
Squareness ASTM F 540
maximum 0.010 in. (0.25 mm)
<0.010"
Residual Indentation ASTM F1914
DIN EN 433
average less than 8%,
max. single reading 10%
< 7%
Flexibility ASTM F 137
no crack or break
No crack or break
Dimensional Stability ASTM Fed. Std. No. 501a
Method 6211, DIN EN 434
<0.020"/ft (0.51 mm/304.8 mm)
<0.015"/ft
Resistance to Chemicals ASTM F 925
DIN EN 423
No more than a slight change in surface dulling, surface attack or staining
no more than a slight change in surface dulling, surface attack, or staining
Resistance to Heat ASTM F 1514
∆<8 ave., max
<∆E=2.0
Resistance to Light ASTM F 1515
∆E<8 ave., max
<∆E=6.0
Static Load Limit Modified ASTM F 970-00
-
>2,500 psi
Smoke Density ASTM E 662
<450
<450
Flame Spread ASTM E 84, NFPA 225
<75
<75
Fire Resistance DIN 4102  
B1
Critical Radiant Flux ASTM E 648, NFPA 253  
>1.08 W/cm2(class I Interior Floor Finish, NFPA Life Safety code 101)
 Abrasion Resistance ASTM D 1044,
CS-10-F Wheel,
500Gm Weight
 
Cycle
10,000
% Gauge Loss
1.60
 Resistance to Wear DIN EN 660-1  
M
Effect of Castor Chair DIN En 425  
No Damage
 Color Fastness ISO 105 B02  
At least 6
Standard for Health Care Faculties NFPA 99  
Confirms to the requirements of NFPA 99 in effect at the time of installation
Fulfils product requirements DIN EN 649  
yes
Underwriters Laboratories UL 779  
Meets UL Standard
WARRANTY
Free from defects in Workmanship and materials*    
Five Years, Optional Lifetime
Conductivity*  
 
Lifetime

Note: The resistant testing as listed below was performed on site and in accordance with the industry accepted standards of EOS-ESD 7.1 at a recent install at client facility.  The ElectraTile ESD Floor Covering was allowed to cure 48 hours prior to testing.  Installation substrate: new, cured concrete utilizing our conductive liquid adhesive and recommended grounding procedures.   Various conditions such as substrate, grades,  and humidity levels may somewhat alter the reading you receive at your facility.

Electrical Properties

ElectraTile RTG Resistance Testing, As installed facility 1

Click for installed RTG, Testing by United

SERIES: Conductive
ELECTRICAL PROPERTIES:
ASTM 150/EOS/ESD S7.1
 RTG: 2.4E04 to 8.3 E05

ElectraTile PTP Resistance Testing, as installed facility 2

Click for installed Point to Point, Testing by United

SERIES: Conductive
ELECTRICAL PROPERTIES:
ASTM 150/EOS/ESD S7.1
PTP: 2.5E04 to 9.9E05

 

Real World Results, Real World ESD Tiles